| DC Disconnects has developed a unique, patented approach to battery safety. The Wall Mount line of battery disconnects improve the installation and safety of any VRLA battery in any type of back up power application.
Fused Wall Mount Disconnect
FWMD-800 -2L FWMD-800-4L
FWMD-250-2L FWMD-250-4L
Proprietary Wall Mount Fuse Pullout Disconnect assembly
Model FWMD-800 accepts 300, 350, 400, 450, 500, 600, 700, and 800-amp TPL fuses.
Model FWMD-250 accepts 70, 80, 90, 100, 125, 150, 200,
225, and 250 amp TPL fuses.
-2L or -4L specifies number of lugs per pole and resulting
enclosure size. External Dimensions of the -4L models are
15.75" x 11.81" x 5". External Dimensions
of the -2L models are 11.81" x 7.87" x 5".
Features:
- UL recognized pull-out fuse holder with 70 to 800-amp
Bussmann TPL fuse. Rated for 80 vdc (UL interrupt 100,000
amps). Also accepts Littlefuse L17T series fuses.
- Non-conductive enclosure.
- Clear Cover for immediate visual inspection.
Cable access holes are to be drilled by
the installer. Use of cord grips on cables is recommended.
|